Population equivalent (PE): how to work out the plant size you need

What population equivalent is, how to calculate it for a house, guest house or restaurant, and why you should neither undersize nor oversize a plant.

Пречиствателна станция БИО-6, доставена и монтирана от ЕРМАКС БГ

Population equivalent (PE) is the unit used to express the load on a wastewater treatment plant: how much pollution and how much water enter it per day, converted into a number of "notional" people. For a single-family house, PE roughly equals the number of permanent residents plus a reserve for guests. For a guest house, restaurant or small hotel the calculation is more involved, and this article walks you through it step by step.

What population equivalent means

The term comes from European wastewater practice. One population equivalent is defined by the organic load an average person produces per day: 60 grams of BOD5. BOD5 is the five-day biochemical oxygen demand, the amount of oxygen bacteria need to break down the organic matter in the water. The more organic matter, the more work the plant has to do.

Besides organic load, sizing also looks at hydraulic load: how many litres enter per day. For domestic properties in Bulgaria, around 150 litres per person per day is usually assumed. You can see this in plant specifications: the BIO-6 treatment plant is rated for 6 PE and 0.9 m³ per day, which is exactly 150 litres per PE.

The two parameters go together. If a site has a lot of water and little pollution, such as beach showers, or little water and a lot of organic matter, such as a food workshop, PE is determined by whichever of the two is less favourable.

How to calculate PE for a family house

For a dwelling the calculation is simple:

  1. Count the people who live in the house permanently.
  2. Add guests who regularly stay for several days, such as relatives in summer.
  3. Think about the coming years: children on the way, elderly parents who may move in, or rooms you may start renting out.
  4. Round up to the nearest standard model.

Example: a family of four who host two relatives every summer has a real load of up to 6 PE. A 6 PE plant covers both everyday use and peaks. A 4 PE plant would be overloaded every time guests arrive.

Population equivalent for guest houses, hotels and restaurants

For commercial and public properties, you count not only who sleeps there but also who works there and who only visits. Designers use different factors, because an office worker or a café customer produces less wastewater than someone who lives and showers on site. That is why PE for such properties is calculated separately for each group.

Property typeHow it is countedWhat to keep in mind
Family houseResidents plus guestsReserve for future needs
Guest houseBeds plus owners and staffFull occupancy in season
Small hotelBeds, staff, restaurant, laundryEach function adds load
Restaurant, caféMeals served and staffThe kitchen also needs a grease trap
Office, workshopEmployees per shiftProcess water is assessed separately

For a guest house with eight double rooms, counting beds alone gives 16 PE. If the owners live on site and there are staff, the load increases. If a kitchen cooks for guests, that is counted too. In such cases the solution usually comes from the BIO 6–25 series, and the exact model is chosen after a site visit.

Calculating from water consumption

If the property already exists and has a water meter, actual consumption is the most reliable starting point. Take the bill for the busiest month, divide by the number of days and you get average daily use in cubic metres. Divide that by 0.15 m³ and you have an approximate PE based on hydraulic load.

Watch out for two things. First, water for irrigation, a pool or car washing does not go into the sewer and must be subtracted. Second, an average day is not a peak day. On a Saturday evening in a guest house consumption can be much higher than the monthly average. The plant must cope with peaks, which is why the designer adds a reserve.

A worked example

Suppose a guest house used 60 m³ of water in August, its busiest month. That is about 1.9 m³ per day. Around 0.4 m³ of that goes on watering the garden and never reaches the sewer. That leaves 1.5 m³ per day, and 1.5 divided by 0.15 gives 10 PE of hydraulic load. If the guest house is full at weekends and half empty during the week, the peak load is higher than the average and the designer will add a reserve. These figures only illustrate the method; they are not a recommendation for a specific model.

Seasonal properties

For villas, mountain lodges and guest houses that only operate in summer or during the ski season, PE is calculated for full occupancy, because that is when the plant has to treat. How the plant will get through the months without load, and how quickly its biology will stabilise when the season starts, is discussed separately.

Why you should neither undersize nor oversize

The most common mistake is buying a plant that is "just enough" because it is cheaper. An overloaded plant cannot break down the organic matter, sludge is carried out with the effluent, odours appear and service visits become more frequent.

The opposite mistake exists too. If a 20 PE plant is installed for two people who only stay at weekends, the bacteria get too little food. The activated sludge weakens and the plant treats worse than a correctly sized smaller one would. The goal is a realistic capacity with a sensible reserve, not the biggest plant available.

  • Undersizing: poor treatment, odours, frequent desludging, trouble with the authorities.
  • Oversizing: higher cost, more electricity, unstable biology under light load.
  • Correct sizing: stable effluent quality, predictable service, lower running costs for years.

More practical advice is in our article on choosing a treatment plant by capacity and site needs.

What information to prepare before asking for a quote

To receive an accurate proposal, have the following ready:

  • number of permanent residents and number of guests at peak times;
  • number of beds if the property is rented out;
  • whether there is a kitchen, restaurant or laundry and for how many people;
  • number of staff per shift;
  • water consumption from bills, if available;
  • whether the property is used all year or seasonally.

With this information the engineer determines the load in PE and m³ per day and selects a model with a suitable reserve. Remember to ask for the plant's documents too: what they should contain is covered in our article on CE marking and the EN 12566-3 standard.

Frequently asked questions

How many PE is one household?

For domestic use, one permanent resident counts as 1 PE. A family of four is about 4 PE, but it is wise to add a reserve for guests and future changes.

How many litres of water is one PE?

For domestic properties, around 150 litres per day is usually assumed. That is why a 6 PE plant is sized for 0.9 m³ of water per day.

How is PE counted for a guest house?

Count the beds, the owners if they live on site, and the staff. A kitchen and laundry add load. The exact figure is set by a designer or engineer after a site visit.

Is it better to buy a bigger plant just in case?

A sensible reserve is useful, but an oversized plant under light load treats less consistently and uses more electricity. Choose capacity based on real peaks.

If you would like us to work out the PE for your property together, contact ERMAX BG. One of our engineers will review the data and the site and send you a technical offer for a plant with the right capacity.

Made byStudio